Please enable JavaScript.
Coggle requires JavaScript to display documents.
Grand Prairie - Coggle Diagram
Grand Prairie
Inspection
LiDar
ultrasonic
CCTV
collection of material samples
object
MH
25 mhs
Sewer
length 2615m
concrete
95m
#
10m ID 1200mm
85m ID 2100mm
CSP
CMP
majority
#
1814m 72% ID 1000-2100mm
706 m 28% ID 300-900mm
diameter 300mm-2100mm
Rehab method
No open cut
cost
Sewer
location
high traffic interseciton
124 Avenue and 100 Stree
As-built information NO
84 Avenue
public park area
As-built information NO
CCTV
9.6/9.6m
PACP quick rating 51
No other issues
Grade 5 Broken Pipe
GZ thinks it is Hole Soil Visible (HSV) still it is Grade 5
PACP
structural Defects
1
O&M Defects
0
CSP
ID 1500mm
61 Avenue Golf and Country Club
As-built information YES
1980
small diameter
ID 400-1000mm
hydraulic grades
0.28%-0.53%
CCTV
782/782m
PACP quick rating 524C C=20-24
Grade 5/4 Deformation and Hole/Wall missing
PACP
structural defects 80
56 surface damage
1 more item...
23 Deformed Flexible
1 more item...
1 Broken Soil Visible
1 more item...
O&M defects 100
50 Deposits Settled
1 more item...
36 infiltration
1 more item...
CSP
ID 400mm
length 76m
ID 900-1050mm
length 706m
Hammer Sounding
suggesting localized areas where voids or
reduced embedment support may be present
116 Avenue
As-built information YES
1986
large diameter CSP
ID 2100mm CSP 2.8mm thickness
small diameter CMP
hydraulic grades
0.38%-0.61%
soil
granular bedding
compacted native backfill
subsurface clay 6m depth
CCTV
1884/2025m
PACP quick rating 41
Grade 4 deforamtion
PACP
structural Defects 50
1 Deformed Flexible
Ovality = 5.3% Grade 4 to be check which kind of DF
46 Surface Damage
Surface Damage Corrosion Grade 3
O&M Defects 49
39 Deposits Settled
Grade 3 10-20%
CSP
ID 2100mm
length 1606m 63 defects
ID 800-1500mm
length 233m 25 defects
ID 300-600mm
length 186m 11 defects