Please enable JavaScript.
Coggle requires JavaScript to display documents.
BSR: emergency diesel genset- 1250KVA 420V, 0.8 pf, 50hz ( Substation 6B…
BSR: emergency diesel genset- 1250KVA 420V, 0.8 pf, 50hz ( Substation 6B area)
-
Note
-
-
-
Emergency Load Summary, 24001-500-CN-1626-001.
-
Misc
-
-
-
-
FAT
-
All electrical and control panels shall be routine, type test and functional test according
to manufacturer standard.
-
-
-
-
-
-
-
-
Weather proof enclosure
-
-
-
louver powered by cranking battery, wired to operate when engine run
Walls shall be 14-gauge minimum, and the roof shall be 12-gauge minimum.
doors - both sides, heavy-duty panic hardware, automatic door closures, and lockable latches.
-
-
-
Synchronizing panel, without CB
Generator Control Panel with Exciter Control and AVR . MVR panel, Synchronizing Panel, Generator control & protection, Generator surge absorber and PT / CT panel,
Generator Neural Circuit Breaker Cubicle, etc.
-
Alternator
insulation class F, temp rise class B
-
voltage drops not exceeding 5% while starting the largest motor 'connected to the emergency switchboard