E* Bath Fan Testing - Coggle Diagram
E* Bath Fan Testing
Bath fan is installed
:check:
Bath Fan No Power - Retest :warning:
Bath fan has power :check:
Test Bath Fan CFM
:check:
Less than 50 CFM :warning:
Check outdoor exhaust flap - Is it painted shut or bug screen is preventing it from opening
.
If stuck shut - try to open safely - Notify builder if not accessible - Retest :warning:
Try both opening sizes on flow hood for your CFM flow results
.
Is fan housing caulked to sheetrock?
If gaps around the bath fan opening this can cause poor CFM results - CWO to seal opening and Retest :warning:
Is installed fan rated to 80 cfm or more?
If less than 80 CFM - Retest :warning:
Is fan noisy
?
If noticeably noisy this could be a fan mechanical issue - Notify Builder - Retest :warning:
Check to see if fan is on high speed - some have a switch
Test at highest speed if still below 50 CFM - Continue to troubleshoot :warning:
50 CFM or more - Passes :smiley:
Bath Fan not installed - Retest :warning:
Only verifying CFM on Bathrooms with a shower