ZEG-7020-620ekw,480V,60Hz- STT P2
-
Engine
auto intake shutoff valve, manual shut off outside the enclosure, reset manual
-
spark arrestor muffler- SS316L, flexible fitting SS316L
-
-
-
-
Pre-lube pump by electric motor driven- zone 1 ( if required), from UCP
-
-
-
Lifting equipment (beam, sling, shackle) - 3rd party cert
-
Control panel
LCP
-
-
-
indicatiors, alarm, shutdown
Ex'd' ,zone 2, IIA, T3, IP56
-
SS 316, outside wall of Enclosure
-
UCP ( loose supply)
IP 31,off skid, in Electrical room
-
-
-
-
-
-
-
-
-
foundation bolt, shim, shipping lock
-
-
-
inteface relay, teminal to FCS
-
-
-
-
-
note
electrical component & instrument - zone 2, IIA, T3
ventilation fan, + prelube pump (if any) +other worked in emergency : zone 1
-
Portable battery & charger ( for UCP, LCP) shall be provided, and sized for enough 2 hrs
-
enclosure
-
weather proof, inspection window
-
-
-
-
-
-
-
-
-
-
-
Radiator: aluminium- marine duty + copper -coating for marine duty; Fan - marine cast aluminium alloy, anti static belt
-
-
Alternator, 620ekw, 480V, 60hz, IP56, class B temp, ATEX
-