Please enable JavaScript.
Coggle requires JavaScript to display documents.
Idemitsu- 1600kw/2000kVA, 400V, 50hz - Coggle Diagram
Idemitsu- 1600kw/2000kVA, 400V, 50hz
Fire & Gas Detection system, (SIL2- option) Fire & Gas Panel
weather proof, acoustic container, offshore
monorail, beam and chain with trolley, hoist for lifting ( if required)
instrument wiring, cable glands, cable trays, junction boxes
-
-
SS316L junction box shall be provided at the edge of skid, Ip56 ( or other need approval)
IP56 rating during standby, IP23 during operation- no need 3rd party, but need testing for approval
-
Engine
LCP on skid, IP 56 (or standard manufacture), SS316L
-
air inlet shut off, manual reset open
-
2 x 100% battery, VRLA- Ex rate-SS316, IP56 or standard manufacture
Accelerometers for engine, for genateror??
-
-
-
Exhaust line -Rockwool, thickness > 25mm
-
duplex fuel filter, oil filter
-
-
-
-
limit spec
-
-
-
fuel tank: on skid- waiting connect point for phase 2, SS 316L material
-
-
-
-
-
A diesel fuel shut-off valve, manual quick shut-off valve
-
Radiator
-
có chỗ ghi Aluminum is preferred, có chỗ ghi not acceptable
Generator
2 x 100% RTD for bearing, winding
-
-
-
space heater kit, 2 x 100%-with 1 spare element wired out for junction box for future
-
Misc
-
-
supervisor for offshore- installation, pre and commissioning (per rate)
class room training and site training (on shore and offshore, offshore- per rate)
No Laptop; ET, software for syn panel
-
Cables: instrument & control cable from UCP to Genset, without cable tray
-