Please enable JavaScript.
Coggle requires JavaScript to display documents.
LPG LIQUEFIED PETROLEUM GAS TERMINAL 2x 1825 kVA PRIME - Coggle Diagram
LPG LIQUEFIED PETROLEUM GAS TERMINAL
2x 1825 kVA PRIME
6.9kV, 3P,50Hz, 0.8pf, temp rise B
PT,CT
tested IEC 60034
PMG
winding+ bearing RTD
Alternator test
Generator control panel
NGR
IP41
NGR at rated 7.2kV/sqrt 3, xx A, xx sec. (Vendor recommendation)
Fuel tank- 2800L
high & high high and low level alarms
fuel piping system (RAL 1003)
oil pump system
breather flame trap
level gauge
air leak test
pressure test
RAL 9006
All power and control/signal cables connected between equipments
Soundproof room
1 meter far from diessel generator room shall shall not exceed 85 dB.
rộng: 11,235m x cao 5,9 m x dài13,573m
Factory Acceptance Test
Testing and commissioning at site, including testing equipments (rental basis).
Rental load bank ( 6.9kV)
sound test
type test certificate
short circuit characters
determination reactance
engine complied ISO 3064
Certificate of conformity
Special tools and accessories.
Spare Parts and Consumables for Installation and Commissioning.
recommend spare part list 2 years ( included all gaskets)
Assembling and installation work at site, including machines…
Training at site for operation and maintenance.
Engine
TVA
spring isolator
crankcase flame trap
crankcase explosion relief valve
Emission meet: QCVN 34:2010/BTNMT