EAF Feeding Operation caused Explosion
Analysis of Disaster
Engaged in iron feeding and steelmaking operations, the workers did not really check whether the iron contained trapped containers (such as gas tanks, oxygen bottles, fire extinguishers, etc.) or iron cans, which will cause explosions because of the high temperature molten iron.
Disaster Prevention
Check whether the electric arc furnace contains a well-closed container or a scrap iron can to prevent exploding and the water in the scrap iron should be drained to prevent the water from vaporizing in the high heat furnace and causing a water vapor explosion.
Hoist Operation causes Fire
Disaster Prevention
Hoist operation should be hung on the main body of the equipment. It is not advisable to hang on other pipes or fittings to avoid breaking and fracturing.
Analysis of Disaster
However, the pipe can not bear the weight of the hanging and then fracture, causing a large amount of high-temperature oil ejected in the pipe then the steam encounters an unknown fire source, causing an explosion and fire.
When removing the flange bolts, there are still two bolts on the inner side that cannot be removed. Therefore, workers used the hoist machine to lift the flange bolts to remove the inside bolts.
Explosion when Turning on the Hydrogen Compressor
Analysis of Disaster
Because the O-ring of the hydrogen compressor unloading valve is damaged, the leaking hydrogen flows into the control panel along the meter air line and a spark is generated when the control panel is activated, the hydrogen accumulated in the control panel is ignited and an explosion occurs.
Disaster Prevention
After a long-term shutdown, when restarting the control panel, it is recommended to continuously blow a non-flammable gas, in order to blow off the accumulated flammable gas and for switches, circuit breakers and relays, it is recommended to place them in an explosion-proof enclosure.
Waterproofing of Water tank Explosion
Analysis of Disaster
The paint contains flammable liquid such as toluene , and its volatilized vapor is ignited and exploded when it encounters the spark of the ruptured lamp.
Disaster Prevention
Ventilation should be adopted to avoid accumulation of flammable substances and lighting fixtures shall be constructed with explosion-proof.
Gas Cylinder Explode during Inspection at Filling Station
Analysis of Disaster
When inspecting gas cylinder, the residual gas in the cylinder should be discharged and the worker starts the fan without explosion-proof function, the spark ignites the gas in the air, causing an explosion.
Disaster Prevention
For places where flammable gases are present, equipment that does not have explosion-proof function shall not be used and ventilation should be strengthened to prevent accumulation of flammable gases.
Aluminum-magnesium Alloy Grinding Operation causes Fire
Analysis of Disaster
When the compressed air is sprayed on the plastic gasket laid on the workbench, high-volt static electricity is generated to ignite the magnesium-aluminum alloy powder.
Disaster Prevention
In the workplace where flammable dust of magnesium-aluminum alloy powder is stored, facilities and equipment for prevention static electricity shall be set.
Fire during Welding and Painting Operations
Analysis of Disaster
The paint was overturned . At that time, the employer stood about 2 meters away, so he didn’t see the overturned paint and keep welding, causing the sparks ignite newspapers and paints and ended up with fire.
Disaster Prevention
keep away from paint and items that are easy to burn.
For places where flammable liquids are present, keep away from fireworks or sources of ignition.
Explosion during Product Synthetic Feeding Operation
Disaster Prevention
The reactor body should be connected to ground and feeding operation should be used conductive devices to remove static electricity.
Analysis of Disaster
The reaction tank body is connected to ground, but the raw material is still fed.
The worker is not required to install a conductive needle according to the standard operating procedure, causing static electricity between the raw material powder and the packaging bag, so an explosion occurs.
Smoking during Work cause Fire
Analysis of Disaster
A worker smoked in the tank where the cleaning naphtha was volatilized, causing a fire.
Disaster Prevention
Implement workers controlled.
Enhance workers education and training.
Strengthen the ventilation in the workplace.
Centrifugal Filtration Operation caused an Explosion
Analysis of Disaster
Due to the hole above the centrifugal filter, the toluene(甲苯) vapor escaped, and the fan did not turn on on the day of the disaster, which makes it impossible to blow off the flammable gas in the workplace and when worker was working with iron tools, he accidentally generated sparks and ignited toluene vapor, causing an explosion.
Disaster Prevention
The centrifugal filter should be completely sealed so the toluene vapor will not escape.
Exhaust equipment should be turned on to avoid accumulation of toluene vapor.
Avoid using iron tools to prevent sparks.